26
Manifold Tank System
Group Name Parameter Name Parameter Value Description Max Value
Fuel Management System
Tanks Number of Tanks (0) Number of tanks in fuel system. 0-48
Tank #
Name (Tank 1) Given name of the tank. abc#
Type Special 1 Type of tank used. Std/Spcl
Manifolded (No) Enable a manifold. Yes/No
Manifold # (1) Number of manifold. 1-24
Manifolds
Manifold #
Name (Manifold 1) Given name of manifold. abc#
Product # (1) Number of product in tanks. 1-48
Delivery Threshold (200.0 gal) Amount of increase to detect delivery. # gal
Theft Threshold (5.0 gal) Amount of decrease to detect theft. # gal
E-Mail
Group Name Parameter Name Parameter Value Description
E-Mail
“From” Address [email protected] Address of sender (console).
SMTP Host your_smtp_host_address IP address of SMTP Host.
SMTP Port 25 Port address of SMTP.
Enable Authentication No Data authentication (if required).
Maximum Queue Size 20 Maximum size of queue in Megabytes.
Retry Timeout 3600 Time, in seconds, that the console will wait before attempting to resend the
message.
Watchdog Timeout 30 Time, in seconds, that the console self-monitoring program waits when it
expects and error due to software or power quality problems.
Events
Group Name Parameter Name Parameter Value Description Options
Rules
Rule – New Rule #
Name (New Rule #) Given name of rule. abc#
Enabled (No) Yes to enable rule. Yes/No
Events
Event
Type (New Alarm Occurred) Event type that triggers action. New Alarm Occurred;
Alarm Status Changed;
Application Event;
Scheduled
Category (Any) System that event occurs in to trigger
action.
Any;
System;
FMS;
VRM;
SCM;
Other
Code (Any) Error/Trouble Event Code that triggers
action.
(see below)
Device (Any) Device that created the alarm
condition.
Various
State (Any) State of alarm to trigger action. Various