General Information
The T5 Series console* with an internal TS-DIMIB Dispenser
Interface Module has built in diagnostic software which
enables an installer to verify communication with the
dispenser / POS system.. This is a menu-based command
line utility which is available through the serial port of the
Power Supply Module. Control Module Firmware version
0.9.5.3685 or greater is required and Power Supply Firmware
version 1.0.1 or greater is required.
Prior to using diagnostic mode
Note:
If the console is not communicating with the
Distribution Box (Dbox), verify that the modules are
at the most current rev. level. If needed, upgrade the
system to current revs, turn off power to the T5 series
console, wait 5 minutes and turn power back on.
Note: If the mapping query is not working, set all hose
positions in set-up to 0 and save conguration.
Check status of the DIM module and wait until the
console shows the DIM is operational. Return to
setup and query dispenser.
In order to use this diagnostic, the console will need to
be placed into an ofine mode which essentially turns the
power supply into a dedicated module for DIM diagnostic
use only. During this time, the T5 console will not be
performing normal operational functions.
To return the console to its normal operation mode, it will
need to be power-cycled. This will allow the Power Supply
to return to its normal state. Note a Power Supply Module
Mismatch alarm will occur and should be ignored.
Procedure
Step 1
Using the LCD panel, select the main menu: FMS (Figure 1).
Figure 1: LCD Home Screen
This will take you to the Menu page. Press the DOWN
button (Figure 2).
Figure 2: Main Menu
This will show the diagnostics screen (Figure 3).
Figure 3: Diagnostics Button
TS-DIMIB Diagnostics
*T5 Consoles include TS-5, TS-550, TS-5000 and TS-EMS
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - TS-DIMIB Diagnostics

1General InformationThe T5 Series console* with an internal TS-DIMIB Dispenser Interface Module has built in diagnostic software which enables an inst

Page 2

2Select the DIM Diagnostic in the Diagnostics section of the Main Menu (Figure 4). Figure 4: Diagnostics ScreenOnce selected you will be prompted to c

Page 3 - Figure 11: DIAG> Screen

3 Figure 10: Setting Baud RateOnce connected hit the Esc key to access the “DIAG>” prompt.Figure 11: DIAG> ScreenStep 3Accessing the Pump Totals

Page 4 - ©2009 FFS 000-0274 Rev A