TS-DIMInstallation Guide Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608 838 8786 • 800 225 9787 • Fax: +1 608 838 6433
10TS-DIM/G to Gilbarco DBox Universal/TS10000TS-DIM/G Adapter Cable(P/N 600-0202 for current loop)(P/N 600-0201 for RS422)Gilbarco Consoleto Controlle
11TS-DIM/G Adapter Cable (P/N 600-0201) TS-DIM/G TS-DIM/G Console to Controller Connector (P/N 601-1004) DB9 to RJ45 Adapters Gilbarco Dbox PA03060020
12Gilbarco G-SITE Controller C2 Style TS-DIM/GS RJ45 to DB9 Adapter (P/N 601-1002) RJ45 to DB25 Adapter (P/N 601-1001) Note: If the 600-0205 cable i
13Pump Specic Installation — TS-DIM / W for Wayne / Dresser Electronic DispenserFollowing the instructions in the TS-DIM General Installation section
14Wayne/Dresser DBoxTS-DIM/WTS-DIM Wayne/Dresser Adapter Cable(P/N 600-0203)Note: See the Wayne/Dresser DBox TS-DIM/W Connection Example Diagram belo
15Wayne Fusion DIM Connection1. Setup the Fusion as described in the “Fusion Installation – HyperPIB-PAM-Console” manual. See step A Below.2. Reboot
16Pump Specic Installation — TS-DIM / T for Tokheim Electronic DispenserFollow the instructions in the TS-DIM General Installation section, and then
17Smart Fuel Controller ConnectionFollow directions below to connect the INCON console to VeriFone’s Smart Fuel Controller (SFC). Using this interface
18Dispensers 1-8 Dispensers 9-16Dispensers 9-16SFC Aux BoardSFC DistributionBoardModified TSP-GDCBL CableDo NOT cut white wireOrange wireFigure 15: Mo
19DIM DiagnosticsExtensive testing and data collection is available to the user through the TS-DIM’s built-in diagnostic port, which is physically loc
2PrefaceThis manual contains instructions for the installation of the INCON TS-DIM (Dispenser Interface Module), which monitors transactions between d
20 Accessing the Internal DiagnosticsThe database section of the diagnostics will show the transaction totals for each fueling position. 1. At the DI
21Clearing the Database Using Privileged ModeNormally, at startup, the totals for all pumps are zero, but, in some situations, the Fueling Positions m
22Using the Internal Diagnostics to Collect Site DataBe prepared, some of these steps involve dispensing at least 1/10 of a gallon of each product fro
23Acquiring and Saving Wayne Dispenser Line FactorsThe following instructions are only applicable for the TS-DIM installations in which the Wayne/Dres
24Programming the Tank GaugeNO. METERS: The total number of all Fueling Point Meters at the site. This is located under the SYSTEM menu. A value abov
25TroubleshootingTroubleshooting Electronic VersionsTable 1 TS-DIM – Diagnostics – Electronic DispensersProblem Recommendation / AnalysisTS-DIM do
26Table 3 Gilbarco MOC G-SITEProblem Recommendation / AnalysisNo data capture. • Is the EMC port on G-SITE enabled?• Is the correct software versi
27TS-DIM Installation on a T5 Series Console Some sites and dispenser congurations may require the use of a second DIM module that would be installed
28Wiring the TS-DIM to a T5 Series ConsoleTurn off the main power source/all power sources that terminate in the console before working on or servicin
29In the programming, you cannot exceed the number of fueling points under DIM 1. Put in the max number of fueling points under DIM 1, the other fueli
3ContentsPreface... 2Abbrev
30©2012 INCON 000-2044 Rev. B3760 Marsh Road ● Madison, WI 53718 U.S.A.Tel: +1 608 838 8786 ● Fax: +1 608 838 6433 ● www.franklinfueling.comTel: USA &
4Important Safety MessagesINCON equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fue
5Description of TS-DIM ComponentsThe TS-DIM collects information on all dispensed product and consolidates the data to a concise, easy-to-read format,
6TS-DIM General Installation Steps – For Electronic Dispensers1. A junction box with a single receptacle outlet must be provided (see the TS-DIM Powe
7TS-DIM Power RequirementsThe TS-DIM must be powered from a dedicated 115 VAC single circuit breaker, with no other devices connected to the power rec
8TS-DIM General Installation Steps – Wiring the TS-DIMWiring the TS-DIM to a Dbox and Power Receptacle1. With all of the power off, install and wire
9Pump Specic InstallationTS-DIM / G for Gilbarco Electronic DispenserGilbarco MOC (Major Oil Company) G-SITE Systems are specially congured. For Gil